Sizing a Fuse

i ( t ) = 2 cos ( ω t ) + 2 cos ( 2 ω t ) + 2 cos ( 3 ω t ) \large i(t) = \sqrt{2} \cos(\omega t) + \sqrt{2} \cos(2\omega t) + \sqrt{2} \cos(3\omega t)

A fuse must continuously carry a current (in amps) described by the formula above.

If fuses are rated in integer multiples of 1 amp RMS, what is the minimum allowable fuse rating?

Note: In order for the fuse not to blow, its rating must exceed the RMS magnitude of the current it carries.


The answer is 2.

This section requires Javascript.
You are seeing this because something didn't load right. We suggest you, (a) try refreshing the page, (b) enabling javascript if it is disabled on your browser and, finally, (c) loading the non-javascript version of this page . We're sorry about the hassle.

0 solutions

No explanations have been posted yet. Check back later!